SIMATIC ET 200SP, CM 4xIO-Link ST Communication module IO-Link Master V1.1
Ex-Stock
General information
Product type designation CM 4 x IO-Link ST
HW functional status FS20
Firmware version V2.2.2
● FW update possible Yes
usable BaseUnits BU type A0
Color code for module-specific color identification plate CC04
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No; Only for PROFINET and configuration as version with FW V2.0 or V2.1
Engineering with
● STEP 7 TIA Portal configurable/integrated from version STEP 7 V15 or higher
● STEP 7 configurable/integrated from version STEP 7 V5.5 or higher
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.3
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V; 20.5 V if IO-Link is used, as the supply voltage for IO-Link devices has
to be at least 20 V at the master.
permissible range, upper limit (DC) 28.8 V
power supply according to NEC Class 2 required No
Input current
Current consumption, max. 45 mA; without load
Encoder supply
Number of outputs 4
Output current
● Rated value 700 mA; Per channel
24 V encoder supply
● Short-circuit protection Yes
● Output current, max. 2.1 A
Power loss
Power loss, typ. 1 W
Hardware configuration
Automatic encoding Yes
● Electronic coding element type H Yes
Digital outputs
Cable length
● unshielded, max. 20 m; Also applies for shielded cables